Insurance-claim power distribution inventory · Six-unit lot · EXW Texas
Delta ElectronicsPower Distribution
Equipment
Available · Sold As-Is

Delta 650kVA Data Center PDUs

Six three-phase, floor-standing power distribution units configured for 480V input and 415/240V output. Each supplied configuration includes five 800A subfeeds, a copper K4 transformer, branch-circuit monitoring and networked touchscreen controls.

Part PDUTA654ACAB4-05 × 800A subfeeds8.75% impedanceEXW Texas

Representative product image and logo courtesy of Delta Electronics. Delta and the Delta logo are trademarks of Delta Electronics, Inc. Proven Performer is an independent reseller and is not affiliated with or endorsed by Delta.

Representative Delta data-center power distribution unit on a white background
Representative manufacturer image · not an offered-unit photographSee actual inventory photos ↓
$180KCurrent six-unit
lot asking price
6 UnitsFive value units + one
heavily damaged unit
650 kVATransformer Rating
480V · 3P3WInput Configuration
415/240V · 3P4WOutput Configuration
Dallas, TexasRecorded Location
Opportunity Overview

A complete configuration summary—not just a headline rating.

The supplied technical summary identifies the PDU architecture, major transformer characteristics, breaker arrangement, monitoring, controls, physical size and every serial number in the lot.

These Delta units are designed to transform and distribute power in data-center and other high-density critical-power environments. The reported configuration takes a 480V three-phase, three-wire input and supplies a 415/240V three-phase, four-wire output.

Each PDU is described as having a copper K4 transformer with 8.75% impedance, five 800A 100%-rated subfeed breakers, individual output branch-circuit monitoring, an RJ45 Ethernet port and a 10-inch LCD touchscreen.

This is an insurance-claim, as-is offering. Condition differs within the six-unit lot, so inspection and electrical testing are central to buyer diligence.

Technical Configuration

Electrical, transformer and control details.

Specifications below are consolidated from the supplied configuration text. Reported certifications should be verified against the offered units' labels or supporting documents.

Electrical System

Supplied configuration
Rated capacity
650 kVA
Input
480V · 3-phase · 3-wire
Output
415/240V · 3-phase · 4-wire
Input main breaker
Not included
Cable routing
Top entry and top exit only
Product designation
Delta 650kVA 480–415/240V FCB

Transformer

Supplied configuration
Conductor material
Copper
Transformer class
K4, as supplied
Impedance
8.75%
Zone rating
Zone 4 compliance, reported
Certification
UL Listed, reported
Verification status
Applicable standard and UL label/file not yet supplied

Distribution

Five subfeeds per PDU
Breaker bases
Five subfeed breaker bases
Installed breakers
5 × 800A subfeed breakers
Breaker rating
100%-rated, as supplied
Branch monitoring
Individual output branch-circuit monitoring
Surge protection
TVSS / SPD not included
Breaker detail
Manufacturer, trip unit and interrupting rating not yet supplied

Controls & Communications

Local + network access
Local interface
10-inch LCD touchscreen
Network interface
RJ45 Ethernet port
Monitoring scope
Individual output branches
Protocol
Not yet supplied
Control model
Not yet supplied
Supporting documents
Configuration text only; no full BOM or submittal received
Included / Not Included

The supplied scope has important boundaries.

Two omissions materially affect application engineering and installation planning: there is no input main breaker and no TVSS/SPD package.

Reported as included

  • 650kVA copper K4 transformer with 8.75% impedance
  • Five subfeed breaker bases in each supplied configuration
  • Five 800A, 100%-rated subfeed breakers
  • Individual branch-circuit monitoring on the outputs
  • RJ45 Ethernet port and 10-inch LCD touchscreen

Reported as not included

  • Input main breaker is not included
  • TVSS / SPD surge protection is not included
  • Bottom cable entry or exit is not supported; top only
  • Full component-level BOM has not been supplied
  • Breaker, monitoring and control part numbers have not been supplied
Condition & Diligence

Condition varies across the lot.

The sell sheet reports transit-related cosmetic damage, transformer-resin observations and one unit with substantial damage. No operational-status representation should be inferred from appearance alone.

Material condition disclosure

One unit has heavy damage, including interior damage.

That sixth unit is described as included with the lot at no additional charge. The published retail-value estimate applies only to the other five units.

What buyers should verify

  • Unit-by-unit inspection: review the available inspection report and reconcile each condition finding to its serial number.
  • Electrical testing: some transformer coils reportedly show slight resin seepage; megger insulation-resistance testing is recommended before finalizing a sale.
  • Transit damage: inspect affected housings and door panels for cosmetic versus functional impact.
  • Certifications: verify the reported UL Listing and Zone 4 compliance from labels or controlled documentation.
  • Application engineering: confirm fault-duty, protection, conductor-routing, grounding and monitoring compatibility.

As-is sale: published specifications summarize currently available information and do not replace an offered-unit nameplate, inspection, test report, engineering review or final sales agreement.

Identification & Freight Planning

Part number, six serials and shipping dimensions.

All six serial numbers are published so a buyer can match inspection findings, photographs and commercial documents to the exact offered units.

Unit identification

Delta part number

PDUTA654ACAB4-0

Supplied serial numbers

Y6726200084B0Y6726200085B0Y6726200086B0Y6726200087B0Y6726200083B0Y6726200088B0

Dimensions & weight

Unit size
82.7 in × 36 in × 78.7 in
Unit weight
6,800 lb
Shipping crate
90 in × 44 in × 95 in
Crated weight
Approximately 7,000 lb
Cable access
Top entry and exit only
Delivery basis
EXW Texas

The supplied text describes one crate at 90 × 44 × 95 inches and approximately 7,000 lb. Confirm whether those figures apply identically to every unit and verify loading equipment before dispatch.

Available Documentation

Start with the full lot overview.

The buyer-facing sell sheet combines the six actual equipment views, condition disclosures and commercial-value context. A unit-by-unit inspection report is reported available upon request.

Public nowSell sheet and complete configuration summary
On requestUnit-by-unit inspection report
Still neededFull BOM, submittal, breaker and controls details
RecommendedMegger testing and label verification
Open Sell SheetRequest Inspection Report

Marketing estimate on supplied sell sheet: $750,000–$900,000 estimated new retail value for five units, stated as based on then-current market pricing. This is not presented as an appraisal, warranty or current resale guarantee.

Delta PDU six-unit liquidation sell sheet
Buyer Questions

What can be answered now—and what still needs diligence.

What exactly is being offered?

Six Delta 650kVA floor-standing PDUs, part number PDUTA654ACAB4-0, offered as an insurance-claim lot. Five units form the published value basis; one heavily damaged unit is included at no additional charge.

Is this a complete BOM?

No. The available text is a useful configuration summary, not a component-level BOM. It does not identify breaker manufacturers or trip units, control-system models, monitoring protocols, SCCR/AIC data or individual internal component part numbers.

Do the units have a main breaker and SPD?

No. The supplied configuration expressly says that the input main breaker and TVSS/SPD surge-protection package are not included.

Are the units operational?

No operational-status representation has been supplied. The lot is sold as-is, one unit is heavily damaged, and megger testing is recommended for units showing slight transformer-coil resin seepage.

Can buyers inspect and obtain reports?

A full unit-by-unit inspection report is reported available upon request. Contact Proven Performer to request that report and coordinate access for qualified buyer diligence.

What should be confirmed before freight is booked?

Confirm exact pickup location, loading capability, whether the 90 × 44 × 95-inch crate and 7,000-pound shipping figures apply to each unit, and the equipment needed for safe handling.

Qualified Buyer Inquiries

Request current terms, the inspection report and an equipment review.

Reference the Delta 650kVA PDU lot or part number PDUTA654ACAB4-0. We can confirm availability, share controlled diligence material and coordinate the next step.

Current lot ask: $180,000 · Six units · EXW Texas · Sold as-is